A duct takeoff counts every duct run and fitting on a set of plans and turns those counts into pounds and labor hours you can price. To do a duct takeoff, measure the linear feet of each duct size and use the perimeter to convert feet to square feet. Multiply by the gauge weight to get pounds. Then count and weigh every fitting, add an allowance for seams and scrap, and multiply total pounds by your hours-per-pound rates. When you know how to do a duct takeoff this way, you price sheet metal by its real weight, set crew hours from your own data, and catch missed fittings before the bid goes out.
This guide covers each step with formulas, a gauge weight table, and a full worked example you can check your numbers against.
Why Does a Duct Takeoff End in Pounds?
A duct takeoff ends in pounds because sheet metal is bought, built, and installed by weight. Linear feet alone hide the real size of the job.
For example, a 36×18 duct in 22 gauge weighs 12.65 lb per foot. A 10×8 duct in 26 gauge weighs 2.72 lb per foot. On a length count, two 100-foot runs of these sizes look the same. One of them has more than four times the metal and needs far more labor.
A complete ductwork takeoff gives you five numbers:
- Linear feet (LF) of straight duct, by size
- Square feet (SF) of sheet metal
- Pounds (lb) of sheet metal
- Fitting and accessory counts
- Shop and field labor hours
How to Do a Duct Takeoff Step by Step
To do a duct takeoff, follow the steps given below.
Step 1: Sort the Plans by System and Pressure Class
Split the ductwork into systems first: supply, return, exhaust, and outside air. Then write down the pressure class of each one. A 2-inch supply main and a 1-inch return main of the same size need different gauges and reinforcement, so they never share a line on your takeoff sheet.
Give each system a short code, such as SA-1 or RA-1, and a color. Mark each run on the plans as you count it. When you finish, any duct that isn’t marked is duct you missed.
Check two more things before you move on:
- Lined duct: Plans often show the clear inside size for lined duct. Add twice the liner thickness to each dimension before you work out the metal. A 24×12 clear size with a 1-inch liner gets built as 26×14.
- Scope breaks: Note where your work stops, such as at a fan, a louver, or another trade’s equipment.
Step 2: Measure Straight Duct in Linear Feet
Measure each straight run from fitting to fitting, and record it by size and system. Stop measuring where an elbow, transition, or tee starts. Fittings get their own count in Step 5, so measuring through them counts the same metal twice.
Use a takeoff sheet with four columns:
- System
- Size
- Gauge
- Linear feet
Start a new line at every size change. Include vertical duct too. Risers, drops to diffusers, and offsets shown in sections add footage that plan views don’t show.
Note short pieces as you go. Shops build straight duct in standard joint lengths, often 4 or 5 feet. A 2-foot piece between two fittings still needs a full set of seams and end connectors, so it takes more labor per foot.
Step 3: Convert Linear Feet Into Square Feet
Multiply the duct’s perimeter in inches by its length in feet, then divide by 12. This is how to calculate square feet of ductwork without drawing every panel. Dividing by 12 turns the inches around the duct into feet of flat sheet.
- Rectangular perimeter = 2 × (width + depth)
- Round circumference = 3.1416 × diameter
- SF per LF = perimeter ÷ 12
- Total SF = SF per LF × linear feet
For example, a 24×12 duct has a 72-inch perimeter. 72 ÷ 12 = 6, so every foot of that duct uses 6 SF of metal.
| Duct size | Perimeter (in) | SF per LF |
| 12×8 | 40 | 3.33 |
| 14×10 | 48 | 4.00 |
| 20×12 | 64 | 5.33 |
| 24×12 | 72 | 6.00 |
| 36×18 | 108 | 9.00 |
| 10″ round | 31.4 | 2.62 |
| 16″ round | 50.3 | 4.19 |
Keep your square-foot totals for each system. External duct wrap and internal liner are taken off from these same numbers.
Step 4: Assign the Gauge and Turn Square Feet Into Pounds
Multiply square feet by the weight of the gauge to get pounds. For each duct width and pressure class, take the gauge from the spec and the SMACNA tables. Duct size alone won’t tell you the gauge.
This table shows galvanized sheet metal weight per square foot by gauge:
| Galvanized gauge | Thickness (in) | Weight (lb/SF) | Common use (varies by spec) |
| 26 | 0.0217 | 0.906 | Small branches and runouts |
| 24 | 0.0276 | 1.156 | Mid-size branches |
| 22 | 0.0336 | 1.406 | Larger mains |
| 20 | 0.0396 | 1.656 | Large mains |
| 18 | 0.0516 | 2.156 | Very large or higher-pressure duct |
| 16 | 0.0635 | 2.656 | Heavy-duty and industrial duct |
The duct weight calculation formula combines Steps 3 and 4:
Rectangular: lb = [2 × (W + D) ÷ 12] × LF × lb/SF
Round: lb = [3.1416 × Diameter ÷ 12] × LF × lb/SF
To get a per-foot number, multiply SF per LF by lb per SF. A 24×12 duct in 24 gauge is 6 × 1.156 = 6.94 lb per foot. This is how to calculate duct weight for any size in one line.
Always use a galvanized chart. Each galvanized gauge number is 2.5 ounces per sq. ft. heavier than the corresponding U.S. Standard Gauge number, regardless of coating weights. An uncoated chart lists 26 gauge near 0.75 lb/SF instead of 0.906. That puts you about 17 percent light on every square foot of 26-gauge duct.
Step 5: Take Off the Fittings
Count every fitting by type, size, and system, then turn each one into square feet. A careful duct fittings takeoff matters for two reasons: fittings take more labor per pound than straight duct, and they’re the easiest items to miss on a busy sheet.
Use these rules for each fitting type:
- Radius elbows: A radius elbow has the same surface area as a piece of straight duct as long as its centerline.
Elbow SF = centerline length (ft) × SF per LF. For a 90° elbow, the centerline length is 1.5708 × the centerline radius.
- Transitions: Use the average perimeter: (perimeter A + perimeter B) ÷ 2 ÷ 12 × length. Weigh the transition at the heavier of the two gauges.
- Offsets: Measure the centerline length and treat it like straight duct of that size.
- Tees and wyes: Take off the body as straight duct, then add the branch as a short stub.
- Bought items: Count spin-ins, volume dampers, fire dampers, access doors, and flex connectors by the piece. Don’t weigh them.
| Fitting | Takeoff method | Unit |
| Radius elbow | Centerline length × SF/LF | lb |
| Transition/reducer | Average perimeter × length | lb |
| Offset | Centerline length × SF/LF | lb |
| Tee or wye | Body + branch stub | lb |
| Dampers, spin-ins, access doors | Count | each |
Mark each fitting on the plan as you count it. Elbows are easy to miss at the ends of runs, and taps are easy to miss where branches leave a main.
On a large job, the fitting count can run into the hundreds, and it often has to be done while several other bids are due the same week. That’s when a missed tap or elbow is most likely to slip through. Many contractors bring in HVAC estimating services during these busy stretches, so every fitting gets counted and weighed while their own estimators focus on pricing and scope.
Step 6: Add Allowances for Seams, Joints, and Scrap
Add a percentage to your flat-sheet pounds for the metal the formula leaves out. The formula only counts the four sides of the duct. Real duct also has:
- Pittsburgh lock or snap-lock seams along its length
- TDC/TDF flanges or slip-and-drive joints at each connection
- Reinforcement angles on larger, higher-pressure duct
- Cut-off scrap from coil and flat sheet
Fittings need a higher allowance than straight runs. Elbow cheeks are cut from square blanks, so about 30% of each cheek blank becomes scrap. Set your own allowance from finished jobs. Compare the pounds of metal the shop actually used with the pounds on the takeoff. The difference is your real allowance.
Step 7: Convert Pounds Into Labor Hours
Multiply total pounds by your hours-per-pound rates, and price shop fabrication and field installation separately. Each rate comes from your own cost codes: total hours divided by total pounds on finished jobs.
Keep the two rates apart because different things change them. Shop speed depends on equipment such as an automated coil line compared with hand layout. Field speed changes with job conditions:
- Ceilings over 12 feet that need lifts
- Occupied buildings or night work
- Crowded ceiling space shared with other trades
- Higher sealing classes on high-pressure systems
After that, add per-piece labor for bought items such as dampers, spin-ins, and access doors.
To turn hours into dollars, start with wage data. The median annual wage for sheet metal workers was $60,850 in May 2024, or $29.26 per hour, according to the U.S. Bureau of Labor Statistics. That’s base wage only. Add payroll taxes, benefits, insurance, and union fringes to get your loaded rate.
Sheet metal labor is often one of the largest line items in a mechanical bid, so a mistake here carries straight through to the final price. Piping, equipment setting, insulation, and controls are priced with the same logic: quantities first, then labor units, then loaded rates. Once you know how to turn duct pounds into dollars, you should know how to estimate mechanical cost for the rest of the scope the same way.
Worked Example: What Does a Full Duct Takeoff Look Like?
Here’s how to do a duct takeoff on a small, low-pressure (2-inch w.g.) supply system with 14-foot ceilings. The gauges come from an example spec.
Straight Duct (Steps 2 to 4)
| Run | Size | LF | Gauge | SF/LF | SF | lb/SF | lb |
| Main | 36×18 | 120 | 22 | 9.00 | 1,080 | 1.406 | 1,518 |
| Branch | 24×12 | 180 | 24 | 6.00 | 1,080 | 1.156 | 1,248 |
| Branch | 14×10 | 150 | 26 | 4.00 | 600 | 0.906 | 544 |
| Runout | 10″ round | 200 | 26 | 2.62 | 524 | 0.906 | 474 |
| Total | 650 | 3,284 | 3,784 |
Fittings (Step 5)
| Fitting | Qty | SF each | Total SF | Gauge | lb |
| 36×18 90° elbow (36″ CL radius) | 2 | 42.4 | 84.8 | 22 | 119 |
| 24×12 90° elbow (24″ CL radius) | 4 | 18.9 | 75.4 | 24 | 87 |
| Transition 36×18 → 24×12, 3 ft | 2 | 22.5 | 45.0 | 22 | 63 |
| Transition 24×12 → 14×10, 2 ft | 3 | 10.0 | 30.0 | 24 | 35 |
| Total | 11 | 235.2 | 304 |
Elbow math: 1.5708 × 36 in = 56.5 in, or 4.71 ft. Then 4.71 × 9.00 SF/LF = 42.4 SF.
The system also has 12 spin-ins with dampers. These are counted by the piece, not weighed.
Total Weight With Allowances (Step 6)
- Straight duct: 3,784 × 1.15 = 4,352 lb
- Fittings: 304 × 1.25 = 380 lb
- Total sheet metal: 4,732 lb
Labor Hours (Step 7)
| Item | Basis | Hours |
| Shop fabrication | 4,732 × 0.010 | 47.3 |
| Field install | 4,732 × 0.030 | 142.0 |
| Height add (14-ft ceiling, +10%) | 142.0 × 0.10 | 14.2 |
| Spin-ins with dampers | 12 × 0.25 hr | 3.0 |
| Total | 206.5 |
Final result: 650 LF of straight duct, 3,519 SF of metal, 4,732 lb, 11 fittings, 12 spin-ins, and 206.5 labor hours. At an example loaded rate of $55/hr, sheet metal labor comes to about $11,360.
Duct is only one part of the bid. Once you know how to turn pounds into hours, use the same approach for equipment, piping, and controls.
Bottom Line
Once you know how to do a duct takeoff in this order, every number comes from the one before it. Feet become square feet, square feet become pounds, and pounds become hours and dollars. Get the gauge right, weigh every fitting, add honest allowances, and check your ratios before the bid goes out.